Centrifugal Horizontal Split Case Fire Pumps
- All Pumps are Hydrostatically Tested to minimum of 150% of its Maximum Working Pressure and can withstand Double the Max.Working Pressure.
- All Pumps have Clock-Wise Rotation when viewed from the Driver Side.
- All Pumps are horizontal single stage Pumps.
- “The rated speed marked on the pump can vary within +/-4% of the listed/ approved rated speed example: 3000 RPM pump can be driven with 2900 RPM Drivers.”
| Model No. | Rated Capacity (GPM) | Size (SucXDis) | UL Listed Rated Net Pressure Range (PSI) | FM Approved Rated Net Pressure Range (PSI) | SETSCO & CE Rated Net Pressure Range (PSI) | Approx Speed (RPM) | Max Working Pressure (PSI) |
|---|---|---|---|---|---|---|---|
| SFP150-25SH | 150 | 6 x 4 | 114-208 | 114-208 | 114-208 | 3500 | 300 |
| SFP150-25SH | 150 | 6 x 4 | 121-220 | 121-220 | 121-220 | 3600 | 300 |
| SFP150-40SM | 150 | 6 x 4 | 206-289 | 206-289 | 206-289 | 2900 | 385 |
| SFP150-40SM | 150 | 6 x 4 | 221-310 | 221-310 | 221-310 | 3000 | 385 |
| SFP150-SN31SH | 150 | 6 x 4 | 226-316 | 226-316 | 226-316 |
Categories: Centrifugal Pumps, PUMPS, SFFECO, Split Case Fire Pumps
Related products
Electric Driven Skids
Features
- Driven by UL Listed Electric Motor.
- Well aligned and Coupled for Direct Operation.
- Skid Packages are Pre-Tested and Inspected thoroughly before release to customers.
- Engineered, coated, hot rolled mild steel to resist corrosion and abrasion.
- Compact skid Design with Small Foot-Print for Retrofit.
- High standard of Quality in material Construction finish and Workmanship
Photoelectric smoke detector
Model No.: LE-SOC-24V
Features
Computer Designed Non-directional Smoke Chamber
360° View of Detector Case
Low Profile, 1.8" Height (with Base)
2 or 4 Wire Base Compatibility, Relay Bases Available
Very Stable Operation, RF/
Standby Current Transient Protection Low, 59μA at 24VDC
Two Built-in Power/Sensitivity Lights for Supervision/Alarm
The automatic sensitivity window check function meets the requirements specified in NFPA 72, Chapters 2 and 7, Inspection, Testing, and Maintenance.
Fire Pump Controllers
Fire Hose Reel Cabinet SF300-SF600
End suction fire pump
LIFECO pumps undergo the required inspection, tests and production control during the assembly process and records are kept for the same, before they are delivered to our customers. Each pump is produced, and subjected to performance tests as follows:
a) Test run
performance curves plotted showing efficiency, brake force (kW), and total head developed at shutdown, at rated capacity, at 150 percent of rated capacity, And at selected intermediate capacities between closing and maximum capacities exceeding 150% of the rated capacity.
b) Hydrostatic Test
Each pump shall be hydrostatically tested for a minimum of 5 minutes. The test pressure shall be up to two times
the maximum working pressure of the pump, but in no case less than 250 psi (1724 kPa) to ensure that there is no
rupture or leakage through the castings at the test pressure.
c) Motor Balance
The impellers of each pump are dynamically balanced with a balance quality grade of G6.3 accordingly
with the requirements for the pumps impellers in the Mechanical Vibration Standard – Balance Quality