iRIS4
| Main Power Supply | 230VAC +10%/-15%,50÷60 Hz |
| Back-up Power Supply- lead batteries | 12V/18Ah |
| Nominally internal battery resistance | <0,3Ohm |
| Storage Temperature | -10˚C to +60˚C |
| Operating temperature | -5°C to +40°C |
| Dust and moisture protection | IP 30 |
| Relative Humidity | up to 95%(without condense) |
| Dimensions | 430/330/120mm |
| Weight | 6kg(without battery) |
iRIS8
| Main Power Supply | 110÷230VAC,50÷60 Hz, 2x200W |
| Back-up Power Supply- lead batteries one in the main block + one in the Block expander | 12V/ 18Ah |
| Nominally internal battery resistance | <0,3Ohm |
| Storage Temperature | -10˚C to +60˚C |
| Operating temperature | -5°C to +40°C |
| Dust and moisture protection | IP30 |
| Relative Humidity (without condense) | up to 95% |
| Dimensions | 430/330/120mm |
| Weight | Min. configuration 7kg/ Max. configuration 15kg (without battery) |
Repeater
| Power Supply: | |
| – from the panel | AUX/GND |
| – external | (24 ±4)VDC |
| Maximum power consumption | 0.11A |
| Communication | RS 485 |
| Twisted pair cable UTP CAT 5: | |
| – maximum length between repeater and panel | max. 1000m. |
| – cross Section | 0.5-2.5mm² |
| Protection class | IP40 |
| Color, Material | White, ABS |
| Dimensions of panel | 200x330x48mm |
| Maximum number of supported panels in network | 64 |
| Network type | Ring topology |
| Memory LOG | 10 000 events |
| Multi language support | YES |
| Operating temperature | -5°C to +50°C |
| Relative humidity resistance. | 95% |
| Weight | ~ 770g |
SensoIRIS CSOU
| Operating Voltage Range | 16 – 32VDC |
| Maximal consumption at communication | 470 μА @ 27VDC |
| Maximal consumption (main tone type 27: | |
| – low volume level | 3 mА @ 27VDC |
| – high volume level | 10 mА @ 27VDC |
| Power volume: | |
| – low volume (up to 100 pcs sounders* to the loop). | ~ 81dB (A) ± 3dB @ 1m |
| – high volume (up to 30 pcs sounders* to the loop) | ~ 88dB (A) ± 3dB @ 1m |
| Wire Gauge for terminals | 0.4 – 2.0mm2 |
| Material and color | ABS / White |
| Dimensions | 105 х 22 mm |
SensoIRIS CSST IS
| Operating Voltage Range | 16 – 32VDC |
| Maximal consumption at communication | 470 μА @ 27VDC |
| Maximal consumption (main tone type 27: | |
| – low volume level | 3 mА @ 27VDC |
| – high volume level | 10 mА @ 27VDC |
| Power volume: | |
| – low volume (up to 100 pcs sounders* to the loop). | ~ 81dB (A) ± 3dB @ 1m |
| – high volume (up to 30 pcs sounders* to the loop) | ~ 88dB (A) ± 3dB @ 1m |
| Wire Gauge for terminals | 0.4 – 2.0mm2 |
| Material and color | SAN, transparent / White |
| Dimensions | 105 х 22 mm |
SensoIRIS GAS
| Power supply | 24VDC |
| Power consumption | <3W |
| Protection against electric shock: | Class III |
| Power connection | hard wired |
| Alarm threshold | 10%LEL |
| Alarms sound level | ≥ 85dB |
| Sensor type | catalytic |
| Sensor lifetime | 5 years |
| Detected gases | LPG/CH4 (Methane) |
| Enclosure color | White |
| Heating-up time | 30 sec |
| Size | 130х96х38mm |
| Weight | 0,200kg |
SensoIRIS M140
| Operating Voltage Range | 15 – 32VDC (Nom. 27VDC) |
| Consumption in quiescent state | < 160μA@27VDC |
| Consumption in alarm state, with communication | 6.5mA |
| Output in alarm state at terminal RI (terminals 4/ 1) | 7.5 mA (max)/ 7.5V |
| Wire Gauge for terminals | 0.4mm² – 2.0mm² |
| Operating temperature | -10°C to +60°C |
| Protection | IP30 |
| Weight (including base) | ~125g |
| Dimensions (including base) | 103x42mm |
SensoIRIS MIMIC
| Operating voltage | 16 ÷ 32VDC |
| Max. current consumption | <2mА @27VDC |
| Current consumption with PCB Status LED ON* | 5.4mA |
| Operating Voltage | 12÷24VDC |
| Voltage for LEDs | 12VDC |
| Max current consumption | 390mA@ 24VDC/ 790mA@ 12VDC |
| Automatic current limitation of the outputs: With Ri=0k With Ri=1k | 15mA 10mA |
| Max. length of connection cable for LEDs | 3m |
| Material/color (enclosure box) | ABS, Grey |
SensoIRIS MiniOut
| Relay switching power | 60W, 62.5VA |
| Relative humidity resistance | (93±3)%@+40°C |
| Operating voltage | 15 ÷ 32V DC |
| Max. current consumption | 0.1mA |
| Relay ratings | 0.25A/24V AC; 2A/30V DC |
| Relay rated current | 2A |
| Relay max. switching current | 5A |
| Protection (with enclosure box) | IP30 |
| Relative humidity resistance | (93±3)%@+40°C |
| Max. cross section of the cables | 2.5mm2 |
| Dimensions (PCB) | 43x25mm |
| Mounting | Indoor use |
SensoIRIS MIO04
| Operating Voltage Range | 15 – 32VDC |
| Consumption, stand-by mode | 175μA@27VDC |
| Nom. current consumption | 200µA@27VDC |
| Outputs, electrical characteristics (max.) | DC 30V/1A; AC 125V/0,5A |
| Wire Gauge for terminals | 0.4mm² – 2.0mm² |
| Operating temperature | -10°C to +60°C |
| Protection | IP40 |
| Weight | ~230g |
| Dimensions | 142x80x45 mm |
SensoIRIS S130 IS
| Operating Voltage Range | 16 – 32VDC (Nom. 27VDC) |
| Consumption in quiescent state, no communication | < 190μA@27VDC |
| Consumption in quiescent state, with communication | < 310μA@27VDC |
| Consumption in alarm state, with communication | 6.5mA |
| Output in alarm state at terminal RI (terminals 4/ 1) | 7.5 mA (max)/ 7.5V |
| Wire Gauge for terminals | 0.4mm² – 2.0mm² |
| Operating temperature | -10°C to +60°C |
| Protection | IP30 |
| Weight (including base) | ~125g |
| Dimensions (including base) | 103x42mm |