iRIS4
| Main Power Supply | 230VAC +10%/-15%,50÷60 Hz |
| Back-up Power Supply- lead batteries | 12V/18Ah |
| Nominally internal battery resistance | <0,3Ohm |
| Storage Temperature | -10˚C to +60˚C |
| Operating temperature | -5°C to +40°C |
| Dust and moisture protection | IP 30 |
| Relative Humidity | up to 95%(without condense) |
| Dimensions | 430/330/120mm |
| Weight | 6kg(without battery) |
iRIS8
| Main Power Supply | 110÷230VAC,50÷60 Hz, 2x200W |
| Back-up Power Supply- lead batteries one in the main block + one in the Block expander | 12V/ 18Ah |
| Nominally internal battery resistance | <0,3Ohm |
| Storage Temperature | -10˚C to +60˚C |
| Operating temperature | -5°C to +40°C |
| Dust and moisture protection | IP30 |
| Relative Humidity (without condense) | up to 95% |
| Dimensions | 430/330/120mm |
| Weight | Min. configuration 7kg/ Max. configuration 15kg (without battery) |
Repeater
| Power Supply: | |
| – from the panel | AUX/GND |
| – external | (24 ±4)VDC |
| Maximum power consumption | 0.11A |
| Communication | RS 485 |
| Twisted pair cable UTP CAT 5: | |
| – maximum length between repeater and panel | max. 1000m. |
| – cross Section | 0.5-2.5mm² |
| Protection class | IP40 |
| Color, Material | White, ABS |
| Dimensions of panel | 200x330x48mm |
| Maximum number of supported panels in network | 64 |
| Network type | Ring topology |
| Memory LOG | 10 000 events |
| Multi language support | YES |
| Operating temperature | -5°C to +50°C |
| Relative humidity resistance. | 95% |
| Weight | ~ 770g |
SensoIRIS CSOU
| Operating Voltage Range | 16 – 32VDC |
| Maximal consumption at communication | 470 μА @ 27VDC |
| Maximal consumption (main tone type 27: | |
| – low volume level | 3 mА @ 27VDC |
| – high volume level | 10 mА @ 27VDC |
| Power volume: | |
| – low volume (up to 100 pcs sounders* to the loop). | ~ 81dB (A) ± 3dB @ 1m |
| – high volume (up to 30 pcs sounders* to the loop) | ~ 88dB (A) ± 3dB @ 1m |
| Wire Gauge for terminals | 0.4 – 2.0mm2 |
| Material and color | ABS / White |
| Dimensions | 105 х 22 mm |
SensoIRIS CSST IS
| Operating Voltage Range | 16 – 32VDC |
| Maximal consumption at communication | 470 μА @ 27VDC |
| Maximal consumption (main tone type 27: | |
| – low volume level | 3 mА @ 27VDC |
| – high volume level | 10 mА @ 27VDC |
| Power volume: | |
| – low volume (up to 100 pcs sounders* to the loop). | ~ 81dB (A) ± 3dB @ 1m |
| – high volume (up to 30 pcs sounders* to the loop) | ~ 88dB (A) ± 3dB @ 1m |
| Wire Gauge for terminals | 0.4 – 2.0mm2 |
| Material and color | SAN, transparent / White |
| Dimensions | 105 х 22 mm |
SensoIRIS GAS
| Power supply | 24VDC |
| Power consumption | <3W |
| Protection against electric shock: | Class III |
| Power connection | hard wired |
| Alarm threshold | 10%LEL |
| Alarms sound level | ≥ 85dB |
| Sensor type | catalytic |
| Sensor lifetime | 5 years |
| Detected gases | LPG/CH4 (Methane) |
| Enclosure color | White |
| Heating-up time | 30 sec |
| Size | 130х96х38mm |
| Weight | 0,200kg |