Split Case Fire Pump
Features
- Capacity: 150 GPM to 3500 GPM
- Working Pressures: 88 to 335 PSI
- Volute Type Thru-Bore Casing
- Frame-Mounted Design
- Small Footprint Ideal for Retrofit
- Dynamically Balanced
- Double Suction Impeller
- Heavy Duty With Heavy Wall Thickness
- 100% Hydrostatic & performance Tested
Attachment
Related products
Centrifugal Vertical Turbine Fire Pumps
- All Pumps are Hydrostatically Tested to minimum of 150% of its Maximum Working Pressure and can withstand Double the Max.Working Pressure.
- All Pumps have Clock-Wise Rotation when viewed from the Driver Side.
- All Pumps are Multistage with 2 stages as minimum requirement.
- “The rated speed marked on the pump can vary within +/-4% of the listed/ approved rated speed example: 3000 RPM pump can be driven with 2900 RPM Drivers.”
| Model No. | Capacity (GPM) | UL,SETSCO & CE Listed Net Pressure (PSI) | Number of Stages | FM Approved Rated Net Pressure (PSI) | Number of Stages | Approx Speed (RPM) |
|---|---|---|---|---|---|---|
| SFP-200-70VT | 200 | 40 - 248 | 2 - 12 | 40 - 289 | 2 - 12 | 1480 |
| SFP-200-70VT | 200 | 48 - 348 | 2 - 10 | 64 - 348 | 2 - 10 | 1480 |
| SFP-200-30VT | 200 | 60 - 305 | 2 - 6 | 2900 | ||
| SFP-200-30VT | 200 | 63 - 323 | 2 - 6 | 2980 | ||
| SFP-200-30VT | 200 | 64 - 327 | 2 - 6 | 3000 |
Thermo-Act Fire Extinguishing System
Thermo-Act fire suppression system
SFFECO Thermo-Act Systems is the advanced technology for automatic fire suppression systems. The systems offer a self-activating suppression system that puts out fires in seconds. It is simple to design and install with low maintenance, cost effective and reliable. Neither electrical nor pneumatic sources should be required for our thermal effect systems. The systems can be used in the presence of an increased risk of fire. SFFECO Thermo-Act systems use fire retardant flexible tube to detect fires. Thus, the fire detection and extinguishing system is not required for detection and discharge. SFFECO Thermo-Act systems can be designed with available commercial agents including clean agents, wet chemicals, foam, and dry powder. The system can be arranged as a direct system or an indirect system.Standard Fire Pumps Systems
Range
- Speed: 2900 – 3500 RPM
- Frequency 50 / 60 Hz
- Capacity 50 GPM – 1500 GPM
- Pressure Range 100 PSI – 261 PSI
Types
- Available as Self Standing Wall Mounted Base Mounted
- Configurations Available EDJ Type EJ Type DJ Type
- Pressure Tanks are available as optional
- SFFECO Control Panels are included in the package
Caprari MEC A
Fire Pump Controllers
Diesel Tanks
EJ Type – Standard Pumps
EDJ Type Models
| Flow (GPM) | Skid Width (mm) | Skid Height (mm) | Skid Length (mm) | Motor (HP) | Jockey (HP/GPM) | Header Pipe |
|---|---|---|---|---|---|---|
| 50 | 700 | 1230 | 830 | 5.5 | 3 / 10 | 1.5" |
| 120 / 150 | 800 | 1250 | 1220 | 15 | 3 / 10 | 2" |
| 250 / 300 | 800 | 1420 | 1220 | 30 | 3 / 15 | 4" |
| 500 | 900 | 1660 | 1350 | 5.5 | 5.5 / 25 |