Flanged X Grooved Ends – 300 PSI
- Complies with AWWA C515 Standard
- High quality graphite stem seal
- NPT plug on body
- 300PSI Working pressure
- -10°C to 82°C Working temperature
- Sizes: 2.5”, 3”, 4”, 5”, 6”, 8”, 10” & 12”
Categories: LIFECO, OS&Y Gate Valves, Valves, Valves
Related products
2 zone fire alarm control panel
Signal Input Module
Horizontal Sidewall Sprinkler
End suction fire pump
LIFECO pumps undergo the required inspection, tests and production control during the assembly process and records are kept for the same, before they are delivered to our customers. Each pump is produced, and subjected to performance tests as follows:
a) Test run
performance curves plotted showing efficiency, brake force (kW), and total head developed at shutdown, at rated capacity, at 150 percent of rated capacity, And at selected intermediate capacities between closing and maximum capacities exceeding 150% of the rated capacity.
b) Hydrostatic Test
Each pump shall be hydrostatically tested for a minimum of 5 minutes. The test pressure shall be up to two times
the maximum working pressure of the pump, but in no case less than 250 psi (1724 kPa) to ensure that there is no
rupture or leakage through the castings at the test pressure.
c) Motor Balance
The impellers of each pump are dynamically balanced with a balance quality grade of G6.3 accordingly
with the requirements for the pumps impellers in the Mechanical Vibration Standard – Balance Quality
Jockey pumps
Emergency Light/Exit Light
LIFECO, Emergency and Exit Lights, Fire Alarm & Low Current System, alarms, Doors , Frames and Exit signs