Description
- Can work as a fixed temperature or rate of rise detector
- Class, selectable from the control panel – A1/R, A2/S, B/S
- Low profile design
- LED indication with 360° visibility
- Built-in isolator
- EN54-5 and EN54-17 certified
| Operating Voltage Range | 16 – 32VDC (Nom. 27VDC) |
| Consumption in quiescent state, no communication | < 170μA@27VDC |
| Consumption in quiescent state, with communication | < 290μA@27VDC |
| Consumption in alarm state, with communication | 6.5mA |
| Output in alarm state at terminal RI (terminals 4/ 1) | 7.5 mA (max)/ 7.5V |
| Wire Gauge for terminals | 0.4mm² – 2.0mm² |
| Operating temperature | -10°C to +60°C |
| Protection | IP30 |
| Weight (including base) | ~110g |
| Dimensions (including base) | 103x42mm |
| Power Supply: From the panel External power supply unit | AUX/GND (24±4)VDC |
| Maximum power consumption | 0.11A |
| Communication | RS 485 |
| Twisted pair cable UTP CAT 5: Maximum length between repeater and panel Cross Section | max. 1000m 0.5-2.5mm2 |
| Degree of protection | IP40 |
| Color, Material | Grey, ABS |
| Operation temperature | -5ºС up to +40ºC |
| Relative humidity | up to 95% (without condense) |
| Storage temperature | -10ºС up to |